Exhibit 2

TABLE VII

MAXIMUM LINE ANGLES ON SPOOL INSULATOR ASSEMBLIES

(ANSI Class 53-4 Spool Insulator)

Designated Maximum Transverse Load = 2,250 Lbs./Conductor

 

WIND SPAN (feet)

CONDUCTOR SIZE

150

200

250

300

350

400

LIGHT LOADING DISTRICT

4 ACSR (7/1)

60

60

60

60

60

60

2 ACSR (6/1)

57

57

56

55

55

54

2 ACSR (7/1)

44

43

43

42

42

41

1/0 ACSR (6/1)

36

35

35

34

34

33

123.3 AAAC (7)

35

35

34

34

33

33

2/0 ACSR (6/1)

35

35

34

34

33

33

3/0 ACSR (6/1)

28

28

27

27

26

26

4/0 ACSR (6/1)

28

27

27

26

25

25

246.9 AAAC (7)

27

26

26

25

25

24

336.4 ACSR (18/1)

26

26

25

24

24

23

336.4 ACSR (26/7)

18

18

17

17

16

16

MEDIUM LOADING DISTRICT

4 ACSR (7/1)

60

60

60

60

60

60

2 ACSR (6/1)

57

56

55

55

54

53

2 ACSR (7/1)

44

43

43

42

41

41

1/0 ACSR (6/1)

36

35

35

34

34

33

123.3 AAAC (7)

35

35

34

34

33

33

2/0 ACSR (6/1)

36

35

34

34

33

33

3/0 ACSR (6/1)

28

28

27

27

26

26

4/0 ACSR (6/1)

28

27

27

27

26

26

246.9 AAAC (7)

27

27

26

26

25

25

336.4 ACSR (18/1)

27

26

26

25

25

24

336.4 ACSR (26/7)

19

18

18

18

17

17

HEAVY LOADING DISTRICT

4 ACSR (7/1)

60

60

60

60

60

60

2 ACSR (6/1)

56

54

53

52

51

49

2 ACSR (7/1)

43

42

41

40

39

38

1/0 ACSR (6/1)

35

34

34

33

32

31

123.3 AAAC (7)

34

34

33

32

31

31

2/0 ACSR (6/1)

35

34

33

32

31

31

3/0 ACSR (6/1)

28

27

26

26

25

24

4/0 ACSR (6/1)

27

27

26

25

25

24

246.9 AAAC (7)

27

26

25

25

24

23

336.4 ACSR (18/1)

26

25

25

24

23

22

336.4 ACSR (26/7)

18

18

17

17

16

16

Replace Table VII in RUS Bulletin 1728F-803, Specifications and Drawings for 24.9/14.4 kV Line Construction, with this table.

 